Reasonable selection of high voltage current limiting fuse
High voltage current limiting fuse is usually considered as a kind of protective apparatus with simple structure, reliable protection and low investment. In fact, although this kind of fuse is simple in structure, it must be strictly controlled in technology and quality to ensure the production of reliable and high-performance products. At the same time, it must be used correctly to give full play to its protection characteristics, otherwise it may lead to the loss of its protection function. The following is a brief introduction to the selection guidelines of this product. For details, please contact our company.
Factors to be considered in selection
In terms of its reliability, it not only affects the performance of the fuse, but also affects the performance of the fuse. Therefore, proper consideration should be given according to the service conditions.
A common installation method is to install the fuse in a three-phase enclosed box. At this time, the fuse must be reduced by 15%. However, the fuse with rated current less than 20A can not be considered to reduce capacity, because small fixed current fuse has less heat and temperature, and the closed environment has little influence on it.
Another installation method is to seal a single fuse in an insulating resin pouring cylinder. In this case, the fuse must be reduced by 25% to ensure that the fuse will not be damaged due to overheating. However, the capacity reduction of fuse with rated current below 20A can still be ignored.
According to the relevant standards, the normal working environment temperature of fuse is between - 25 ℃ and + 40 ℃. When the temperature is lower than - 25 ℃, the mechanical properties of fuse will be affected. When the temperature is higher than + 40 ℃, the capacity of fuse should be reduced. Generally, the capacity of fuse should be reduced by 1% every 1 ℃ increase.
For the fuse installed in the three-phase unclosed cabinet, due to the mutual interference between the temperature rise of the three-phase fuse, the fuse can be reduced by 10%. However, fuse with rated current less than 20A is still not considered.
Generally, for the fuse with small rated current less than 10a, due to the long-term corona discharge on the melt, the melt is easy to be aged, so the fuse should be kept away from the grounding metal frame as far as possible.
Users sometimes use two or three fuses in parallel in order to increase the current level of fuse. At this time, the mutual influence factors of temperature should also be considered. Generally, the fuse capacity can be reduced by 10% ~ 20%.
It should be noted that the fuse must not be simply used in series in a higher voltage circuit.
Reasonable selection of high voltage current limiting fuse
Installation and replacement
Before installation, first check whether the fuse appearance is complete, good and clean. If it has been dropped or vibrated violently, check its resistance value and carefully check whether there are cracks on the surface of porcelain tube. During installation, pay attention to the direction of the impactor marked on the fuse. After the correct installation, lock the spring clip (or fastening bolt) on the base to prevent too loose contact.
In the three-phase system, when one fuse acts, three fuses should be replaced, unless it can be confirmed that only one fuse passes through the short-circuit current, because although the other two do not act, they may have been seriously damaged or nearly damaged.
It is necessary to be very careful when replacing the fuse, because the current limiting fuse has a reliable action range during operation, but it can not guarantee that every fault condition is within its reliable range, such as the tripping failure of the switch device, or the action of the fuse under the minimum breaking current. For the sake of safety, it is necessary to wait at least 10 minutes after the fuse acts and the circuit is isolated by other electrical appliances, and the fuse must be replaced without electricity.
In the general power system, if the choice is appropriate, the fuse should rarely act. If this is not the case, it may be that the system selection and coordination is improper or the fuse calculation and selection is wrong, which should be further checked and calculated.
For the normal operation of the fuse, its life can be more than 10 years. During regular maintenance of equipment, the change of internal resistance of fuse can be measured to judge whether it is aging, and the change range of internal resistance should be within ± 10%.